Adjust
boilers for optimum efficiency and conform to
emission levels with Model 1207 Handheld Flue Gas Analyzer.
The unit quickly measures and calculates all the parameters
for accurate flue gas analysis. Simultaneously display eight
different measurements in user selectable language. Model
1207 Analyzer can store up to 150 time/date stamped combustion
tests and can transfer the data to a printer or IBM compatible
PC for later analysis. Analyzer features 11 preprogrammed
fuels, self calibration, and CO alarm preset at 1000 ppm.
Measure Nitric Oxide with the optional NOx sensor. Unit
includes probe, protective sleeve, 110 VAC power adapter,
carrying case and manual.
SPECIFICATIONS
Ranges: O2: 0-21%; CO: 0-4000 ppm; CO2: 0-99.9%;
NO: 0 to 5000 ppm; Temp. (Flue and nett): 32-1112°F (0-600°C);
Efficiency: 0-99.9%; Poison Index: 0-99.9%; Excess Air:
0-2885%.
Accuracy: O2: ±0.2%; CO: ±20
ppm <400 ppm, ±5% >400 ppm; CO2:
±0.3% of rdg.; NO: ±5 ppm <100 ppm, ±5% >100 ppm;
Temp.: ±5°F (±2°C), 0.3% of rdg.; Efficiency: ±1.0% of rdg.;
Poison Index: ±0.01; Excess Air: ±0.2%.
Resolution: O2: 0.1%; CO: 1
ppm; CO2: 0.1%; NO: 1ppm; Temp.: 1.0°F/C;
Efficiency and Excess Air: 0.1%; Poison Index; 0.01%.
Ambient Operating Temperature: 32 to 104°F (0 to
40°C).
Power: 110 VAC adapter (220 VAC optional).
Computer Requirements: IBM compatible 386 or above
and Windows® 3.1 or later with 2MB RAM and 2MB hard drive
disk space, one serial port.
Pre-Programmed Fuels: Natural gas, Town gas, Light
oil, Heavy Oil, Coke, Coal, Anthracite, Propane, Butane,
Kinsale gas, and Gascor.
Probe: 11-1/4" (28.6 cm) length, stainless steel,
Type K thermocouple, 9 ft (3 m) neoprene hose.
Weight: 2.2 lb (1 kg).
Agency Approvals: CE.
ACCESSORIES
-- See "Ordering" page
1206-1 Infrared Printer.
1207-6 220 VAC Adapter.
1206-71 Replacement Filter. |