The Series
1300 Smart Indicators/Transmitters are extremely
versatile digital process controls, ideal for use with Dwyer®
pressure, temperature and flow sensors. Microprocessor based,
all models are fully programmable and accept common thermocouple,
RTD, current or voltage inputs. An integral 20 VDC power
supply suitable for powering all Dwyer® 2-wire transmitters
is standard. Bright LED display automatically indicates
temperature range in °F (°C) based on selected thermocouple
or RTD input. For flow monitoring or control with Dwyer®
differential pressure transmitters, a preprogrammed SQRT
function may be selected to display actual engineering units
in CFM, GPM, etc. In addition, a user defined linearization
table is provided for non-linear functions, i.e., liquid
level indication in a side mounted cylindrical tank. Four
independent alarm status LED displays are fully programmable
to indicate process condition at a glance.
The Series 1300 is available with a variety
of output options including multiple alarm relays, analog
retransmission (current), bridge excitation (voltage) and
serial communications. Alarms are fully programmable: Hi,
low, deviation, deadband, time delay, manual or automatic
reset and NO or NC operation. Current retransmission may
be any part of the indicated range and the high value of
the retransmission range may be lower than the low value
(inversion). Consult factory for specifications and availability
of optional outputs not listed.
SPECIFICATIONS
Selectable Inputs: Thermocouple (J type stocked),
field selectable K, T, R, S, E, F, N, or B type; RTD (100
O DIN); Current or Voltage.
Input Impedance: Thermocouple (1 MO min.); RTD Current
(1 mA max.); Current (51 O) and Voltage (1 MO).
Dual Relay Output: DPST with shared common. Fully
programmable for High, Low or Deviation Alarm, deadband,
time delay, manual or automatic reset, NO or NC operation
(factory wired NC in power-off state). Contacts rated 8A
max., 100 mA min., @ 240 VAC (<100 mA switching current
may require removal of factory wired varistors across relay
contacts) and 8A max. @ 30 VDC.
Current Retransmission Output: Spannable 4-20 mA,
0-20 mA or 0- 10 mA; 0 mA min.22 mA max.; Loop resistance:
0-700 O (integral loop powered), 0-1000 O (externally powered
10-30 VDC).
Integral Power Supply (for 4-20 mA, 2-wire transmitter
input): 20 VDC, 50 O input impedance.
Power Requirements: 120 VAC, 50/60 Hz (as stocked);
field configurable 240 VAC 50/60 Hz.
Accuracy (@ 20°C): Thermocouple input ±1°C Cold Junction
Error ±1°C (J, K, T type), ±2°C (R, S, E, F, N type) or
±3°C (B type); RTD input ±0.1% of reading ±0.1°C; Current
input ±0.1% full span; Voltage input ±0.02% full span (0.1,
1, 10 volts), ±0.04% full span (1-5 volts).
Displays: 5-digit, 7 segment 14 mm (0.5") high LED
display; Four independent alarm status LED indicators; 3.3
Hz update rate.
Display Resolution: User-adjustable.
Memory Backup: Nonvolatile memory.
Serial Communications: Optional RS485.
Operating Temperature: 10 to 40°C (Linearized and
cold junction compensated).
Electrical Connections: Removable terminal blocks
for ease of wiring.
Isolation: Power Supply to 1.5 kV; Inputs to 500V;
Relay Outputs to 500V; Current Retransmission Output to
500V (typical).
Weight: 1 Ib, 14 oz (850 g).
Options: 24 VAC 50/60 Hz Supply Voltage; SPDT Relay
Output; Programmable 2-20 VDC or Constant 24 VDC Outputs;
RS485 Serial Communications.
Agency Approvals: CE.