The Model
1950G Explosion-Proof Switch combines the best
features of the popular Dwyer Series 1950 Pressure Switch
with the benefit of natural gas compatibility. Units are
rain-tight for outdoor installations, and are UL listed
for use in Class I, Groups A, B, C, & D; Class II, Groups
E, F, & G and Class III atmospheres, ATEX for EExd IIB
& Hydrogen T6, and CSA & FM approved for Class I,
Div. 1, Groups B, C, D; Class II, Div. 1, Groups E, F, G
and Class III atmospheres. The 1950G is very compact, about
half the weight and bulk of equivalent conventional explosion-proof
switches.
Easy access to the SPDT relay and power supply
terminals is provided by removing the top plate of the aluminum
housing. A supply voltage of 24 VDC, 120 or 240 VAC is required.
A captive screw allows the cover to swing aside while remaining
attached to the unit. Adjustment to the set point of the
switch can be made without disassembly of the housing.
SPECIFICATIONS
Service: Air and compatible combustible gases.
Wetted Materials: Consult factory.
Temperature Limits: 0 to 140°F (-17 to 60°C). Note:
Set point drift may occur with ambient temperature changes.
Pressure Limits: 45" w.c. (11.2 kPa) continuous;
10 psig (68.95 kPa) surge.
Enclosure Rating: IP64, NEMA 3, 7 and 9.
Switch Type: 1 Form C relay (SPDT).
Electrical Rating: 10A, 120/240 VAC, 28 VDC. Resistive
50mA, 125 VDC.
Power Requirements: 24 VDC ±10%. 120 or 240 VAC ±10%
optional.
Electrical Connections: Internal terminal block.
Process Connections: 1/8" female NPT.
Mounting Orientation: Diaphragm in vertical position.
Consult factory for other position orientations.
Set Point Adjustment: Screw type on top of housing.
Weight: 2 lbs. 15.7 oz. (1.35 kg).
Agency Approvals: CE, UL, CSA, FM, ATEX.
|