Series
2600 Temperature/Process Controllers set a new
standard for quality, versatility, ease-of-use and value.
While they include a high level of standard features, many
function setup items appear in the control menu only when
the function is selected, so you don’t have to wade through
unnecessary items. Units feature a universal input for thermocouple
types J, K, E, T, L, N, B, C, S & R; RTDs 100O Plt.
NIST, 100O Plt. DIN, 120O Ni Industrial, 1000O Plt. DIN;
differential input (-10 to +10 mV DC)and process input (0
to 20 mA DC, 0 to 10 VDC). A standard 24 Volt isolated,
regulated power supply is included to operate most standard
4-20 mA transmitters.
Standard features include Self-Tune, Fuzzy
Logic, fully adjustable PID, Auto/Manual control with bumpless
transfer and front panel activation key, percent output
indication, peak and valley indication, loop break protection
and indication. For process inputs, the display is fully
programmable from -1999 to +9999 with selectable decimal
point location. Most thermocouple and RTD inputs can show
whole or tenth degree displays. The Series 2600 is available
with single or dual setpoint outputs and can be programmed
for on-off, PID or heat/cool or latching alarm. All outputs
are isolated from the inputs. Outputs include 10 Amp relay
and 0-20 mA DC (scalable).
SPECIFICATIONS
Selectable Inputs: Thermocouple, RTD, DC voltage
or DC current.
Input Impedance:
Thermocouple - 3 Megohms
minimum.
Voltage - 5000 ohms.
Current - 10 ohms.
RTD Current - 200 µA
maximum.
Display: Two 4-digit, 7 segment, 0.56" (14.2 mm)
high LED.
Accuracy: ±0.25% of span, ±1 least significant digit.
Supply Voltage: 100 to 240 VAC nominal, +10%-15%,
50 to 400 Hz, single phase; 132 to 240 VDC +10% -20%.
Operating Temperature: 14 to 131°F (-10 to 55°C).
Control Output Ratings: Relay: SPDT, 10 A @ 240 VAC
resistive, 1/2 hp @ 120 VAC, 1/3 hp @ 240 VAC; Alarm
Relay: SPST, 3 A @ 240 VAC resistive; Proportional Current:
0-20 mA DC, scalable into 600 ohms maximum.
Weight: 13 oz (369 g).
Front Panel Rating: NEMA 4X (IP65).
FEATURES
- NEMA 4X (IP65) Front Panel Resists Dust & Moisture
- Four Password Protected Security Levels
- Front Panel Programmability
- 16 Segments of Ramp/Soak with Program End Control
- Operates on 100-240 VAC, 132-240 VDC