The Series
3000SGT Photohelic® Switch/Gage/Transmitter combines
several critical control functions into a single, easy-to-install
package. This versatile instrument starts with the universally
accepted standard for reliable low air pressure measurement,
the Dwyer® Magnehelic® Gage. It measures positive, negative
or differential pressures within ±2% of full scale accuracy.
This time-proven component provides highly reliable analog
indication of air or compatible gas pressure on a 4", 80°
scale. Gage operation is completely independent — functions
normally even if power is interrupted to electrical elements
of the control.
Next, two DPDT relays are added which serve as Low/High
limit controls (or pressure switches) capable of handling
up to 10 amps @ 28 VDC or 120/240 VAC directly. Individual
setpoint deadband is one pointer width — less than 1% of
full scale; just enough to assure positive, chatter-free
operation. Integral holding coils enable user to connect
the two so they work like a single control with variable
deadband — ideal for applications such as clean room and
building pressurization, HVAC systems, automatic air filter
or level control and much more. Actuation points are fully
adjustable over the entire pressure range with convenient
front mounted knobs linked to bright red setpoint indicators.
Finally, the Series 3000SGT Photohelic® Switch/Gage includes
a separate 4-20 mA, 2-wire transmitter operating from an
external 10-35 VDC power supply. Separate adjustments are
included for zero and span inside the rear electronics enclosure.
Optional A-700 Power Supply is a perfect companion rated
for AC inputs from 100-240V; DC outputs from 24-28V. The
transmitter component is an ideal driver for variable speed
blowers and fans, damper positioners and for continuous
data logging on computerized VAV systems or strip chart
recorders.
Besides the obvious cost and space saving advantages of
combining all these control functions in a single unit,
think of the additional savings in time and material with
just one set of pneumatic lines to connect instead of three
or four.
SPECIFICATIONS
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: See model chart on "Ordering" page.
Pressure Limits: See model chart on "Ordering" page.
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Process Connections: 1/8" female NPT.
Size: 4" (101.6 mm) dial face, 5" (127 mm) O.D. x
8-1/4" (209.55 mm).
Weight: 3 lb 14.5 oz (1.77 kg).
SWITCH SPECIFICATIONS
Switch Type: Each set point has 2 Form C relays (DPDT).
Repeatability: ±1% of full scale.
Electrical Rating: 10A @ 24 VDC or 120 VAC, 6A @
240 VAC.
Electrical Connections: Screw terminals.
Power Requirements: 120 VAC, ±10%.
Mounting Orientation: Diaphragm in vertical position.
Consult factory for other position orientations.
Set Point Adjustment: Adjustable knobs on face.
TRANSMITTER SPECIFICATIONS
Accuracy: See model chart on "Ordering" page.
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Pressure Limits: See model chart on "Ordering" page.
Thermal Effects: ±0.025% F.S./°F (0.045% F.S./°C).
Power Requirements: 10.0 to 35 VDC (2-wire).
Output Signal: 4-20 mA DC.
Zero & Span Adjustments: Multi-turn potentiometers,
internally accessible.
Response Time: 250 mSec.
Loop Resistance: 0-1250 ohms.
Current Consumption: 38 mA DC, maximum.
Electrical Connections: Terminal block.
Warm-up Time: 10 minutes.
OPTIONS -- Consult Factory
for Pricing
-TAMP Tamper-Proof Knobs - require special spanner-type
key (included) to adjust set points.
ACCESSORIES
-- See "Ordering" Page
A-298 Flat Aluminum Bracket
A-700 Power Supply
|