Chamber Type Level Switches
 

 

 

 

Adjustable deadband combined with direct 2-1/2" threaded or 2-1/2" flange mount makes the reliable, heavy duty 500 Series ideal for liquid level control in large or small tanks. Chambers are available in cast iron, cast steel or cast 316 stainless steel to meet the most demanding application. Float rods are available from the standard 6" (152.4 mm) up to 24" (610 mm) long providing action down to a specific gravity of 0.55. 2-1/2" (64 mm) float is suitable for pressure of 400 psig (28 bar), 2-1/2" x 4" (64 x 102 mm) float is suitable for 200 psig (14 bar). Maximum operating temperature is 425°F (218°C). A variety of circuits can be ordered including SPST, SPDT or DPDT with hermetically sealed snap action or mercury contacts. Single pole, double throw electrically independent circuits are available as well as contact for high or low DC current applications. A full range of enclosures are available such as general purpose, weatherproof, explosion-proof or explosion-proof/vapor proof.

APPLICATIONS
Oil refineries, chemical plants, power generating stations, pumping stations, heat transfer systems, sanitary/waste water facilities, drip legs, hydraulic systems, boilers.

SPECIFICATIONS
Service: Compatible liquids. Cast iron is not for use with lethal or flammable substances either liquid or gaseous.
Wetted Materials:
Body: Cast iron, cast steel, or 316 SS.
Float and Trim: 316 SS.
Temperature Limit: 425°F (218°C).
Pressure Limit: 400 psig (27.6 bar).
Enclosure Rating: NEMA 4X. Optional general purpose or explosion-proof.
Electrical Rating: Snap Switch: 12A @ 120 VAC, 5A @ 240 VAC, 0.5A @ 125 VDC resistive, 0.25A @ 250 VDC resistive. Mercury Switch: 4A @ 120 VAC/DC, 2A @ 240 VAC/DC. Higher contact ratings available for the mercury switch.
Electrical Connections: Screw terminal.
Conduit Connection: 3/4" female NPT.
Process Connection: 2-1/2" male NPT. Optional 2-1/2" flange.
Mounting Orientation: Vertical.
Set Point Adjustment: At minimum deadband setting the set point is adjustable approximately ±1/2" (12.7 mm).
Weight: 35 lb (15.9 kg).
Agency Approvals: UL.
Deadband: Adjustable between 0.5" (12.7 mm) to 3" (76.2 mm).
Specific Gravity: 0.8 minimum. Optional 0.55 minimum.
Float and Rod Insertion Length: 6.5" (165.1 mm). Optional 12" (304.8 mm), 18" (457.2 mm), or 24" (609.6 mm) rod length. Longer float rods give larger adjustable deadband.

    DIMENSIONAL DRAWING

500

     
    CATALOG
    ORDERING
     
 
Pressure
Flow
Air Velocity
Level
Temperature
Valves
Combustion Testing
Data Acquisition
Humidity
Test Equipment
Accessories