The Series
604D Minihelic® differential pressure Indicating Transmitter
combines visual monitoring with electronic control of low
differential air or compatible gas pressures. This versatile
device is ideal for building HVAC systems where local indication
is needed during maintenance checks or when troubleshooting
the system. The transmitter design employs the latest strain
gage technology and operates in 2-wire control loop circuits.
Separate Zero and Span controls plus a 4-screw terminal
strip are protected in a gasketed side enclosure. Cable
gland fits .10-.25" round cable. A 10-35 VDC power supply
is required.
SPECIFICATIONS
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: ±5 F.S.O.
Stability: ±1% F.S./yr.
Pressure Limits: 30 psig (206.8 kPa) continuous;
50 psig (344.7 kPa) surge.
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Process Connections: Barbed, for 3/16" (4.76 mm)
I.D. tubing.
Size: 2-1/16" (52.39 mm) diameter dial face.
Weight: 5.6 oz (159 g).
Agency Approvals: CE.
TRANSMITTER SPECIFICATIONS
Accuracy: ±2% of full span output (includes linearity,
hysteresis and repeatability).
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Compensated Temperature Range: 32 to 120°F (0 to
48.9°C).
Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C).
Power Requirements: 10-35 VDC (2-wire*).
Output Signal: 4 to 20 mA.
Zero and Span Adjustments: Internally accessible
potentiometers.
Loop Resistance: DC; 0-1250 ohms maximum.
Current Consumption: DC; 38 mA maximum.
Electrical Connections: Terminal block.
Mounting Orientation: Diaphragm in vertical position.
Consult factory for other position orientations.
*Optional 3, 4 wire configurations available, contact
factory.
|