The Series
605 Magnehelic® Indicating Transmitter provides
for both visual monitoring and electronic control of very
low differential pressure. The Series 605 is ideal for control
applications in building HVAC systems where local indication
is desired during routine maintenance checks or necessary
when trouble shooting the system. The easily read dial gage
is complimented by the two-wire, 4-20 mA control signal
utilizing the time-proven Dwyer® Magnehelic® gage mechanical
design and Series 600 transmitter technology. The two-wire
design with terminal strip on the rear simplifies connection
in any 4-20 mA control loop powered by a 10-35 VDC supply.
SPECIFICATIONS
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: See chart.
Stability: ±1% F.S./yr.
Pressure Limits: See chart on "Ordering" page.
Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Process Connections: 1/8" female NPT.
Size: 4" (101.6 mm) dial face, 5" (127 mm) O.D. x
2-11/16" (68.3 mm).
Weight: 1 lb, 12.6 oz (811 g).
Agency Approvals: CE.
TRANSMITTER SPECIFICATIONS
Accuracy: See chart (includes linearity, hysteresis,
repeatability).
Temperature Limits: 20 to 120°F(-6.67 to 48.9°C).
Compensated Temperature Range: 32 to 120°F (0 to
48.9°C).
Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C).
Power Requirements: 10-35 VDC (2-wire).
Output Signal: 4 to 20 mA.
Zero and Span Adjustments: Protected potentiometers.
Loop Resistance: DC; 0-1250 ohms maximum.
Current Consumption: DC; 38 mA maximum.
Electrical Connections: Screw terminal block.
Mounting Orientation: Diaphragm in vertical position.
Consult factory for other position orientations.
ACCESSORIES
-- See "Ordering" Page
A-298 Flat Aluminum Bracket
for flush mounting
A-370 Mounting Bracket, flush mount Series
605 Transmitter in bracket. Bracket is then surface mounted.
Steel with gray hammertone epoxy finish.
|