The Series
629 Differential Pressure Transmitter monitors
differential pressure of air and compatible gases and liquids
with 0.5% accuracy. The design employs dual pressure sensors
converting pressure changes into a standard 4-20 mA output
signal for two wire circuits. Small internal volume and
minimum moving parts result in exceptional response and
reliability. Terminal block zero and span adjustments are
easily accessed under the top cover. The Series 629 Differential
Pressure Transmitter is designed to meet NEMA 4X (IP66)
construction.
APPLICATIONS
Monitor Differential Pressure Across:
- Flow Elements
- Heat Exchangers
- Filters
- Pumps
- Coils
SPECIFICATIONS
Service: Compatible gases and liquids.
Wetted Materials: Type 316, 316L SS.
Accuracy: ±0.5% F.S. (includes linearity, hysteresis,
and repeatability).
Temperature Limits: 0 to 200°F (-18 to 93°C).
Compensated Temperature Limits: 0 to 175°F (-18 to
79°C).
Pressure Limits: See chart on "Ordering" page.
Thermal Effect: 0.02%/°F (0.036%/°C) includes zero
and span.
Power Requirements: 13 to 30 VDC.
Output Signal: 4 to 20 mA. Optional 0-5, 1-5, 0-10,
1-6 or 2-10 VDC.
Response Time: 50 msec.
Loop Resistance: 0-1300 ohms maximum for current
output. For voltage outputs, minimum load resistance: 2000
ohms.
Electrical Connections: Terminal block; 1/2" female
NPT conduit.
Process Connection: 1/4" female NPT.
Enclosure Rating: Designed to meet NEMA 4X (IP66).
Mounting Orientation: Mount in any position.
Weight: 10.1 oz (286 g).
Agency Approvals: CE.
NOTE: Pressures exceeding the working pressure
limit may cause a calibration shift of up to ±3% of full
scale. |