The Series
641RM is the ideal instrument for monitoring
air flow. This transmitter uses a heated mass flow sensor,
which allows for precise velocity measurements at various
flow rates and temperatures. The 641’s 16 field selectable
ranges from 0-250 to 15,000 FPM (0-1.25 to 75 MPS) provide
it the versatility to be selected for a multitude of applications.
The units 6' cable which connects the sensing probe with
the electronic enclosure allows the enclosure to be mounted
where it can be more easily accessed. Longer cable lengths
are available fro ducts that are at very high elevations
from the plant floor. The optional LED produces a complete,
compact solution for local indication of air flow.
SPECIFICATIONS
Service: Clean air and compatible, non-combustible
gases.
Accuracy:
3% FS Process gas: 32 to 122°F (0 to 50°C).
4% FS Process gas: -40 to 32°F & 122 to 212°F
(-40 to 0°C & 50 to 100°C).
Response Time: Flow: 1.5 seconds to 95% of final
value (output filter set to minimum).
Temperature Limits: Process: -40 to 212°F (-40 to
100°C). Ambient: 32 to 140°F (0 to 60°C).
Pressure Limit: 100 psi (6.89 bar) maximum.
Humidity Limit: Non-Condensing.
Power Requirements: 12–35 VDC, 10–16 VAC.
Output Signal: 4-20 mA, isolated 24V source, 3 or
4-wire connection.
Output Filter: Selectable 0.5 –15 (seconds).
Loop Resistance: 600 ohms max.
Current Consumption: 300 mA max.
Electrical Connections: Screw terminal.
Mounting Orientation: Unit not position sensitive.
Probe must be aligned with airflow.
Weight: 13.2 oz (374.26 g).
Cable Length: 6 ft (1.82 m).
Probe Length: 12" (30.48 cm) standard.
Probe Diameter: 5/16" (0.79 cm).
OPTIONAL
DISPLAY VERSION:
Display: 4-1/2 digit 1/2" red LED.
Resolution: 1 FPM, 0.01 MPS (10 FPM @ 10,000 and
15,000 FPM ranges).
Weight: 13.9 oz (394.16 g).
ACCESSORIES -- See "Ordering" page
A-155 - Mounting Gland with 1/2" male
NPT fitting
A-156 - Flange Mounting Plate with 1/2" female NPT
|