The Series
650 Temperature Transmitter combines low cost
with small size making it ideal for a wide variety of HVAC,
industrial and commercial multi-point temperature monitoring
applications. Non-polarized terminals simplify connection
to any 12-35 VDC power supply. Capable of operation with
long cable runs, Series 650 Transmitters are well suited
for monitoring air or water temperatures at remote locations.
Three models in popular ranges factory calibrated within
0.3% of span. All are linear within 0.25% of span and may
be recalibrated within low range and span limits shown in
chart. Low range is temperature corresponding to 4 mA output.
Span is temperature difference between Low and High ranges
corresponding to 4-20 mA output signal.
SPECIFICATIONS
Input: Silicone-junction transistor.
Output Signal: 4-20 mA DC.
Power Requirements: 12-35 volts DC.
Accuracy: ±0.3% F.S. @ 20°C (68°F).
Linearity: Within 0.25% of span
Thermal Drift: Less than 0.5% of span over ambient temperature
range of 0 to 50°C (32 to 122°F).
Probe Construction: 6" long, 0.25" O.D. Type 304
Stainless Steel.
Ambient Operating Temperature: 0 to 70°C (32 to 158°F).
Temperature Limits (Probe): 204°C
(400°F).
Probe Cable Length: 7 ft (2.1 m).
Voltage Stability: Output error less than 0.01% of
span over the specified supply voltage range.
NOTE: Consult factory for special ranges calibrated
within the limits of -55°C and 180°C.