Linearized
output for precise temperature monitoring or
control is combined with small size and quick, easy mounting.
Rugged Series 651 Transmitters are designed for use with
2 or 3-wire Pt100 RTDs (to DIN standard 43760 or BS1904)
or ungrounded Type K thermocouples. Thermocouple Models
651TC are cold junction compensated, automatic 32 to 160°F
(0 to 70°C) with upscale burnout. These economical devices
provide the accuracy and reliability you need at the lowest
possible cost.
SPECIFICATIONS
Input: 2 or 3- wire Pt100 RTD (models 651A), or ungrounded
Type K thermocouple models 651TC).
Output: 4-20 mA DC, linearized.
Transmitter Type: 2-wire.
Output Impedance: 700@ 24 VDC
Power Requirements: 10-32 VDC, reverse connection
protected.
Accuracy: ±0.2°C plus 0.2% reading (models 651A),
±0.1% FS plus cold junction errors (models 651TC).
Temperature Drift: ZERO drift typical 0.02%/°C (0.09°F),
SPAN typical 0.005%/°C 0.0036°F).
Ambient Operating Temperature: 32 to 122°F (0 to
50°C).
Maximum Storage Temperature: 160°F (70°C)
Response Time: 10-90% in 200 ms (models 651A), 70%
in 2 ms (models 651TC).
Agency Approvals: CE.
ACCESSORIES
-- See "Ordering" Page
A-709 Optional enclosure for Series 651 Transmitters.
NEMA 1 protective housing is 3" x 2 1/8" (76 x 54 mm). Supplied
with mounting hardware, strain relief fitting and assembly
instructions.
|