Our low
cost Series 668 Differential Pressure Transmitter
is capable of measuring low pressures with a ±1% accuracy
- ideally suited for proper building pressurization and
air flow control. Transmitters can withstand up to 10 psig
overpressure with no damage to the unit. Variable capacitance
sensor design provides excellent sensitivity and long-term
stability. Compact, lightweight design makes installation
simple and easy. Units also feature reverse-polarity protection.
SPECIFICATIONS
Service: Air and non-conductive gases.
Accuracy: ±1% of full scale (RSS), (includes non-linearity,
hysteresis, and non-repeatability).
Temperature Limits: Operating: 0 to 150°F (-18 to
65°C), Storage: -40 to 185°F (-40 to 85°C).
Pressure Limits: 10 psig (0.7 kg/cm²).
Compensated Temperature Range: 0 to 150°F (-18 to
65°C).
Thermal Effects: 0.033% FS/°F (0.18% FS/°C).
Supply Voltage: 12-30 VDC.
Output: 4 to 20 mA, 2-wire.
Zero and Span Adjustment: ±1 mA, non-interactive.
Response Time: <60 msec.
Loop Resistance: 0-800 ohms.
Electrical Connection: Terminal strip.
Pressure Connection: 3/16" O.D. fitting for 1/4"
I.D. tubing.
Housing: Fire retardant glass filled polyester.
Weight: 3 oz (85 g).
Agency Approvals: CE.
|