Series
677 Differential Pressure Transmitters are designed
to measure pressures as low as 0.1" w.c. with ±0.4% accuracy.
Use Series 677 for building energy management systems, environmental
pollution control, oven pressurization, lab and fume hood
control, HVAC and VAV applications. The transmitter features
10 psid overpressure, reverse polarity protection and EMI/RFI
protection. Internal regulation permits use with unregulated
DC power supplies.
SPECIFICATIONS
Service: Air and nonconductive, noncorrosive gases.
Wetted Materials: Brass.
Accuracy: ±0.4% full scale (RSS).
Temperature Limits: 0 to 175°F (-18 to 79°C).
Pressure Limits: 5 times full scale or 10 psi, (whichever
is greater).
Thermal Effects: <±0.033% F.S. over 40 to 100°F
range.
Power Requirements: 9 to 30 VDC.
Output Signal: 4 to 20 mA DC, 2-wire.
Span and Zero Adjustments: Externally accessible
potentiometers, noninteractive, ±10% F.S. adjustment.
Response Time: 250 msec maximum.
Loop Resistance: 0 to 800 O (calibrated using 250
O load @ 24 VDC).
Electrical Connections: Three screw terminals.
Process Connection: 3/16" O.D. barbed brass pressure
fitting for 1/4" push-on tubing.
Housing: Fire retardant glass-filled polyester.
Weight: 10 oz (283 g).
Agency Approvals: CE. |