Differential Pressure Transmitters
 

 

 

Series 677 Differential Pressure Transmitters are designed to measure pressures as low as 0.1" w.c. with ±0.4% accuracy. Use Series 677 for building energy management systems, environmental pollution control, oven pressurization, lab and fume hood control, HVAC and VAV applications. The transmitter features 10 psid overpressure, reverse polarity protection and EMI/RFI protection. Internal regulation permits use with unregulated DC power supplies.

SPECIFICATIONS
Service: Air and nonconductive, noncorrosive gases.
Wetted Materials: Brass.
Accuracy: ±0.4% full scale (RSS).
Temperature Limits: 0 to 175°F (-18 to 79°C).
Pressure Limits: 5 times full scale or 10 psi, (whichever is greater).
Thermal Effects: <±0.033% F.S. over 40 to 100°F range.
Power Requirements: 9 to 30 VDC.
Output Signal: 4 to 20 mA DC, 2-wire.
Span and Zero Adjustments: Externally accessible potentiometers, noninteractive, ±10% F.S. adjustment.
Response Time: 250 msec maximum.
Loop Resistance: 0 to 800 O (calibrated using 250 O load @ 24 VDC).
Electrical Connections: Three screw terminals.
Process Connection: 3/16" O.D. barbed brass pressure fitting for 1/4" push-on tubing.
Housing: Fire retardant glass-filled polyester.
Weight: 10 oz (283 g).
Agency Approvals: CE.

 

    DIMENSIONAL DRAWING


     
 

SERVICE MANUAL
 

CATALOG
    ORDERING
     
 
Pressure
Flow
Air Velocity
Level
Temperature
Valves
Combustion Testing
Data Acquisition
Humidity
Test Equipment
Accessories
ATEX Products