Models
A-900 and A-901 are the perfect instrument housing
for indoor and outdoor applications. Protects controls from
dirt, dust, oil and water. Unit is rated weatherproof type
NEMA 4X and has a fully gasketed cover. Standard features
include a lockable latch to prevent tampering and flush
mounting hardware.
The Model
A-900 comes standard with a 1/4 DIN cut out in the
front cover. Controller will mount with front face exposed
for easy access to the programming buttons. Love and Mercoid
controllers feature weatherproof NEMA 4X rated front panels
and gaskets enabling the control to be weatherproof protected
when installed in the A-900 even though the front face is
exposed. Wiring an installed control is easy due to the
hinged cover and spacious clearance for the control to swing
out with front cover. The lockable latch prevents unauthorized
removal of the control from the enclosure.
The Model
A-901 comes standard with a clear plastic front window
and mounting hardware to install the control inside the
box. Controller mounts just behind the window assuring easy
viewing. Mounting the control inside the enclosure protects
the control face from corrosive atmospheres or from being
covered in oil, dirt and dust. The lockable latch prevents
unauthorized removal of the control and removes access to
the control programming buttons. The mounting hardware is
attached to the rear of the enclosure and includes a bracket
with a 1/4 DIN cutout and standoffs long enough for Love
and Mercoid controls to fit. Control programming buttons
are easily accessible by just opening the front cover.
SPECIFICATIONS
Service: Indoor or outdoor.
Rating: Nema 1, 2, 3, 3R, 4, 4X, 12 and 13.
Materials:
Body: UV stabilized fiberglass
reinforced polyester.
Snap Latch: 304 SS.
Hinge: Stainless Steel.
Mounting Feet and Screws: 304 SS.
Window: UV stabilized polycarbonate.
Cover Gasket: Neoprene.
Agency Approvals: UL 508.
Control Temperature Limits:
When using the enclosures with controls that have 10A relay
outputs the extra heat generation decreases the maximum
ambient temperature value that the control can be used at
inside the enclosure. Other outputs on our controls are
not a concern.
For Models: 25XX3, 26XX3, 26X3X, 26X33, MPC
| Ambient
Temperature |
Maximum
Current |
| A-900 |
A-901 |
77°F (25°C)
104°F (40°C)
131° (55°C) |
10 Amps
10 Amps
7.5 Amps |
10 Amps
9 Amps
6 Amps |
FEATURES
- UV stabilized for outdoor use.
- Snap latch with lockable hasp.
- Continuous cover hinge.
- Fiberglass material is easily punched or drilled for
conduit connections.
- Includes feet an screws for flush mounting to a wall.
- Compatible with Love 2500, 2600, LCU204, LCU104, and
Mercoid MPC.
|