The Series
HFO Flow Alarm provides continuous monitoring
and control of flow rate levels. The flow alarm can be configured
to open or close a contact for an increasing or decreasing
set point. The unit includes two 10A SPDT limit switches
with field adjustable alarm settings. Integral direct reading
scale provides local indication of flow rate. The flow alarm
is designed to mount in any orientation and does not require
inlet or outlet straight plumbing. The Series HFO is constructed
with a rugged cast aluminum NEMA 4X (IP65) enclosure for
installation outdoors or in harsh environments.
APPLICATIONS
Monitoring flow in chemical processing, waste water processing,
lubrication systems, process control, solar systems, drain
lines and pump testing.
SPECIFICATIONS
Service: Compatible gases or liquids.
Wetted Materials:
Body: Aluminum, brass or 304 SS.
Seals: Buna-N or Fluoroelastomer.
Magnet: PTFE coated Alnico.
Other Internal Parts: 304 SS.
Viscosity: 500 SSU.
Temperature Limits: 240°F (116°C).
Pressure Limits: Aluminum Body: 600 psig (41 bar);
Brass Body: 3500 psig (240 bar); 304 Stainless Steel Body:
6000 psig (413 bar).
Enclosure Rating: NEMA 4X (IP65).
Accuracy Measuring: ±4% FS over entire range; ±2.5%
over center third of the measuring range.
Repeatability: ±1% of full scale.
Switch Type: SPDT, 10A @ 250 VAC; 0.5A @ 125 VDC
(resistive).
Shipping Weight: 1/4 to 1/2" female NPT Models: 3 lb
(1.4 kg); 3/4 to 1" female NPT Models: 4.5 lb (2.0 kg);
1-1/2" female NPT Models: 12 lb (5.4 kg).
PRESSURE
DIFFERENTIAL VS. FLOW RATE
1/4" FEMALE NPT
|
1/2"
FEMALE NPT
|
3/4",
1" & 1-1/2" FEMALE NPT
|
|