Monitor
and control relative humidity and temperature
in building energy management systems with the Series HT
Humidity/Temperature Transmitter. Designed for demanding
HVAC/EMCS applications, the Series HT provides ±3% RH accuracy
and ±1% stability per year. Routine calibration is not required
with the fully interchangeable sensor. Two wire connections
allow easy instillation directly into air ducts or within
a controlled area.
SPECIFICATIONS
Relative Humidity Range: 10 to 90% RH.
Temperature Range: Duct mount: -40 to 140°F (-40
to 60°C), wall mount: 23 to 131°F (-5 to 55°C).
Accuracy: ±3% RH @ 25°C, ±0.3°C @ 25°C.
Temperature Limits: Duct mount: 14 to 140°F (-10
to 60°C), wall mount: 23 to 131°F (-5 to 55°C).
Storage Temperature: -40 to 140°F (-40 to 60°C).
Operating Humidity Range: Duct mount: 0 to 100% RH,
wall mount: 0 to 90% RH.
Power Requirements: 10 to 28 VDC.
Output Signal: 4 to 20 mA.
Response Time: 15 seconds.
Current Consumption: 4 mA minimum.
Conduit Connection: 1/2" NPT.
Mounting Connection: 3/4" NPT.
Drift: ±2% RH over 2 years.
Temperature Sensor: Pt 1000O RTD.
RH Temperature Dependence: <±1.5% RH from 14 to
140°F (-10 to 60°C).
Temperature Dependence: 0.01°C/°C.
Housing Material: ABS plastic.
Enclosure Rating: Duct mount only IP65.
Weight: 0.6 lb (0.3 kg).
Agency Approvals: CE.
ACCESSORIES
-- See "Ordering" page
HT5 - Replacement Sensor.
|