Rapidly
obtain accurate measurements of airflow distribution
in HVAC systems. The versatile design of the AFH electronic
balometer allows easy data acquisition on ceiling, wall-mounted,
and floor-level diffusers, working in supply or exhaust.
View measurements easily on the large LCD display, and store
up to 100 readings in its nonvolatile memory for later analysis.
Download data to your computer via the A-547 RS-232 cable
(sold separately). Eliminating time-consuming calculations,
this instrument utilizes a sixteen-point measurement array
to display flow in cfm, m³/h, or l/s. Light weight and easy
to handle, the AFH requires only one person to operate.
Standard 2' x 2' hood fits over most standard grills and
exhausts. Additional hood expansion kits are sold separately.
Each unit includes: AFH meter, 2' x 2' hood, rugged carrying
case, four universal hood-support poles, four AA batteries
and calibration data sheet.
SPECIFICATIONS
Service: Air.
Volume Flow Rate: 30 to 1180 cfm (50 to 2000 m³/h).
Temperature Limits: 32 to 176°F (0 to 80°C).
Accuracy: ±2% of reading.
Temperature Accuracy: ±0.5% of reading.
Display: 4 digit LCD, 0.45" high.
Output: RS-232 serial interface.
Memory Capability: 99 readings.
Volume Flow Resolution: (1 m³/h, l/s, or cfm).
Temperature Resolution: 0.1°C or 1°F.
Velocity Resolution: 1 fpm (0.01 m/s).
Power Requirements: 4 AA batteries (included).
Pressure Drop Across: 0.22" H2O
max. (55 Pa).
Weight: 26.55 lb (12.04 kg).
Agency Approvals: CE.
|