Demanding
humidity/temperature applications require the Series RH
Transmitter which offers high accuracy, long
term stability, and reliable operation. The Series RH is
designed for monitoring and controlling humidity or both
humidity and temperature in building energy management systems,
HVAC, commercial, residential, clean rooms, museums, climate
chambers, and other space monitoring applications.
The Series RH is a two-wire transmitter with a 4-20 mA loop
powered output. The state of the art sensor recovers from
100% saturation and is calibration-free. The Series RH is
available in duct mount or OSA (outside air) models. Select
humidity monitoring or humidity and temperature models.
The combined humidity/temperature version (RHT) provides
dual 4-20 mA output signals to control both humidity and
temperature with one sensor which reduces installation costs.
The dual version is also available with an optional alpha-numeric
LCD to provide local indication of humidity and temperature
simultaneously. The displayed temperature is field selectable
for °F or °C.
SPECIFICATIONS
Relative Humidity Range: 0 to 100% RH.
Temperature Range: -40 to 140°F (-40 to 60°C).
Accuracy: ±2% @ 10-90% RH; ±0.9°F @ 72°F (±0.3°C
@ 25°C).
Temperature Limits: -40 to 140°F (-40 to 60°C).
Storage Temperature: -40 to 176°F (-40 to 80°C).
Compensated Temperature Range: -4 to 140°F (-20
to 60°C).
Power Requirements: 10-35 VDC.
Output Signal: 4-20 mA, 2 channels for humidity/temperature
models (loop powered on RH).
Response Time: 15 seconds.
Electrical Connections: Screw terminal block.
Conduit Connection: Duct Mount: 1/2" NPS; OSA: 1/2"
(22.3 mm).
Drift: <1% RH/year.
RH Sensor: Capacitance polymer.
Temperature Sensor: Solid state band gap.
Housing Material: Duct Mount: PBT; OSA: Polycarbonate.
Enclosure Rating: NEMA 4X (IP65) for OSA mount
only.
Display: Optional 2-line alpha-numeric, 8
characters/line.
Display Resolution: RH: 0.1%; 0.1°F (0.1°C).
Weight: Duct Mount: 0.6 lb (0.3 kg); OSA:
1 lb (0.45 kg).
Agency Approvals: CE.
|