Regulate
temperatures for heating or cooling control with
Series TSS Dual Stage Temperature Switch. The Series TSS
is designed to accept two inputs (thermistor or RTD) with
independent 8A relay output for dual stage temperature control.
The unit also features a 30 mA TTL alarm output for activating
an external buzzer.
The Series TSS offers 34 programmable parameters
to customize control functions. Access to all parameters,
except setpoint, can be secured with a password code. The
TSS Series includes a rear terminal cover and instruction
manual. Input sensors are sold independently.
APPLICATIONS
TSS Digital Temperature Switches are suitable for industrial
chillers, environmental chambers, walk-ins and freezers,
heat sealers, sterilizers, beer and wine chillers, mug frosters,
coolers, display cases and cabinets, warmers, meat and produce
storage, floral preservation, refrigerated transportation,
laboratories, food service equipment, ovens and dryers,
tobacco preservation, hot melt glue stitchers for case erectors,
cool rooms, burn-in rooms and chambers, and cold water citrus
packing.
SPECIFICATIONS
Probe range: -58 to 302°F (-50 to 150°C).
Input: PTC thermistor (1000O @ 25°C), or RTD (PT100O
@ 100°C).
Output: One 8A SPDT relay @ 250 VAC, resistive; One
8A SPST relay @ 250 VAC resistive; Alarm: TTL 30 mA @ 12
VDC.
Horsepower Rating (HP): 1/3 HP.
Power Requirements: 12 VAC/DC.
Accuracy: 0.5% of full scale.
Display: 3-digit and sign, red.
Resolution: 0.1° (<100°); 1° (=100°).
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 32 to 131°F (0 to
55°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Dimensions: 76 x 34 x 60 mm (3 x 1.3 x 2.4 in).
Front Panel Rating: NEMA 4X (IP65).
Weight: 2.3 oz (65 g).
Agency Approvals: CE, UR, URc.
PARAMETERS
| |
Description |
Units |
Range |
| Set 1 |
Temperature
Set Point 1 |
Degrees |
r4 to r6 |
| Set 2 |
Temperature
Set Point 2 |
Degrees |
r5 to r7 |
| r0 |
Set1 and
Set2 dependency |
Range |
Ind/dEP |
| r1 |
Differential
for Set1 |
Degrees |
0.1 to 20.0 |
| r2 |
Differential
for Set2 |
Degrees |
0.1 to 20.0 |
| r3 |
Band differential |
Degrees |
0.1 to 20.0 |
| r4 |
Minimum
value for Set1 |
Degrees |
-99.9 to
r6 |
| r5 |
Minimum
value for Set1 |
Degrees |
-99.9 to
r7 |
| r6 |
Maximum
value for Set1 |
Degrees |
r4 to 302 |
| r7
| Maximum
value for Set1 |
Degrees |
r5 to 302 |
| r8 |
Operation
mode |
Range |
On1/On2/nEU |
| A0 |
Alarm differentials |
Degrees |
0.1 to 20.0 |
| A1 |
Maximum
probe 1 alarm |
Degrees |
0.1 to 99.9 |
| A2 |
Maximum
probe 2 alarm |
Degrees |
0.1 to 99.9 |
| A3 |
Minimum
probe 1 alarm |
Degrees |
0.1 to 99.9 |
| A4 |
Minimum
probe 2 alarm |
Degrees |
0.1 to 99.9 |
| A5 |
Alarm check
time (*) |
hh:m |
0.0 to 18.0 |
| c0 |
Minimum
relay stop time |
Minutes |
0 to 240 |
| c1 |
Operation
output 1 |
Range |
dir/inv |
| c2 |
Operation
output 2 |
Range |
dir/inv |
| c3 |
Default
operation output 1 |
%ON |
0 to 100 |
| c4 |
Default
operation output 2 |
%ON |
0 to 100 |
| P0 |
Temperature
units |
Range |
°C/°F |
| P1 |
Temp. probe
1 adjustment |
Degrees |
-20.0 to
20.0 |
| P2 |
Temp. probe
2 adjustment |
Degrees |
-20.0 to
20.0 |
| P3 |
Decimal
point |
Option |
no/yES |
| P4 |
Probe to
be displayed |
Option |
sd1/sd2 |
| P5 |
Number of
temp. probes |
Range |
1/2 |
| H0 |
Set default
settings |
Command |
0 |
| H1 |
Keypad protection |
Option |
no/yES |
| H2 |
Operation
led OUT |
Option |
dir/inv |
| H3 |
Operation
led def |
Option |
dir/inv |
| H4 |
Communication
setup |
Numeric |
0 to 999 |
| H5 |
Access code
to parameters |
Numeric |
0 to 999 |
| H6 |
Probe type |
Option |
ptc/pt1 |
*Time Format: hh:m, where m are tenths of minutes.
ACCESSORIES -- See "Ordering" Page
TS-5 PVC Probe, 5 ft (1.5 m) cable
TS-51 PVC Probe, 10 ft (3 m) cable
TS-6 Metal Probe, 5 ft (1.5 m) cable
TS-61 Metal Probe, 10 ft (3 m) cable