Photohelic®
Switch/Gages function as
versatile, highly repeatable pressure switches combined
with a precise pressure gage employing the time-proven Magnehelic®
gage design. The Photohelic® switch/gage measures and controls
positive, negative or differential pressures of air and
compatible gases. Standard models are rated to 25 psig (1.7
bar) with options to 35 (2.4) or 80 (5.5 bar) psig. Single
pressure 36000S models measure to 6000 psig (413 bar) with
a 9000 psig (620 bar) rating. Two phototransistor actuated,
DPDT relays are included for low/high limit control. Easy
to adjust setpoint indicators are controlled by knobs located
on the gage face. Individual setpoint deadband is one pointer
width - less than 1% of full scale. Setpoints can be interlocked
to provide variable deadband - ideal for control of fans,
dampers, etc. Gage reading is continuous and unaffected
by switch operation, even during loss of electrical power.
Choose from full scale pressure ranges from a low 0-.25"
(0-6 mm) w.c. up to 30 psi (21 bar); single positive pressure
to 6000 psig (413 bar).
PHOTOHELIC
SENSING - HOW IT WORKS
In typical applications, these Dwyer switch/gages control
between high and low pressure set points. When pressure
changes, reaching either set point pressure, the infrared
light to the limiting phototransistor is cut off by the
helix-driven light shutter. The resulting phototransistor
signal is electronically amplified to actuate its DPDT slave
relay and switching occurs. Dead band between make and break
is 1% of full scale or less - just enough to assure positive,
chatter-free operation.
RELAY-TRANSFORMER
FEATURES
A plastic housing protects all electronic components. Solid-state
and integrated circuit electronics are on glass-epoxy printed
circuit boards and self-extinguishing terminal boards (for
the Series A3000 only).
APPLICATIONS
- PHOTOHELIC® SWITCH/GAGES
In both series of pressure switch/gages, you get the convenience
of a visual indication plus high-low limit switching. For
both OEM and in-plant applications, the Photohelic® switch/gage
is used to control pressures in air conditioning systems,
clean rooms, fluidic and pneumatic control systems, materials
handling equipment, alarm or control fume exhaust systems,
control pressure in air structures, and monitor respiratory
and blood pressures.
STANDARD
MODEL
Two phototransistor-actuated circuits and two DPDT relays
permit both high and low alarms or limit controls. Relays
are de-energized when gage pointer is to the left of respective
set points; relays are energized as pointer passes to the
right of set points. Loss of electrical power or loss of
pressure provide "fail safe" protection.
SPECIFICATIONS
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult Factory.
Accuracy: ±2% of full scale at 70°F (21.1°C). ±3%
on -0 and ±4% on -00 models.
Pressure Limits: -20" Hg. to 25 psig (-0.677 to 1.72
bar). MP option; 35 psig (2.41 bar), HP option; 80 psig
(5.52 bar). 36003S – 36010S; 150 psig (10.34 bar). 36020S
and higher; 1.2 x full scale pressure.
Temperature Limits: 20 to 120°F. (-6.67 to 48.9°C)
Low temperature option available.
Process Connections: 1/8" female NPT.
Size: 4" (101.6 mm) dial face, 5" (127 mm) O.D. x
8-1/4" (209.55 mm).
Weight: 4 lb (1.81 kg).
SWITCH SPECIFICATIONS
Switch Type: Each setpoint has 2 Form C relays (DPDT).
Repeatability: ±1% of full scale.
Electrical Rating: 10A @ 28 VDC, 10A @ 120, 240 VAC;
Electrical Connections: Screw terminals. Use 167°F
(75°C) copper conductors only.
Power Requirements: 120 VAC, 50/60 Hz; 240 VAC &
24 VAC Power optional.
Mounting Orientation: Diaphragm in vertical position.
Consult factory for other position orientations.
Set Point Adjustment: Adjustable knobs on face.
Agency Approvals: UL,CSA, CE.
HIGH AND
LOW LATCHING CIRCUITS
Dwyer Photohelic® switch/gages can be wired for high-latching,
low-latching or combination high-low latching
circuits. That is, the equipment will hold in these respective
positions once activated and until manually reset. This
can be particularly useful for alarm and signal applications
where control is accomplished by another Photohelic® switch/gage
or other means. Complete wiring and operational instructions
are included. Where manual reset is required a dry circuit
push button such as Dwyer Part A-601 should be used.
OPTIONS
-- Consult Factory for Pricing
-SR Single contact, right set point, for actuation
on increasing or decreasing pressure.
-OEM OEM Model, less relay and transformer components
and housing but including infared diodes and phototransistor(s),
light shutter and set pointer(s). For single or double contact.
-RMR Remote-Mounted Relay, relay pack may be mounted
remotely from gage. Standard length is 5 ft. For other lengths,
specify cable length required.
-TAMP Tamper-proof knobs, low temperature option,
special scales, voltages and other features and modifications
are available.
Special Housings available include Weatherproof (NEMA
4) and Explosion-proof (NEMA 7 & 9; NEC Cl I, Gr C&D;
Cl II, Gr E, F&G; Cl III). Contact Customer Service
for detailed dimension drawings.
Special Purpose Ranges
Scale No. 3401 Square Root Specify Range
Scale No. 3402 Blank Scale Specify Range
ACCESSORIES
-- See "Ordering" Pages
A-298 Flat Flush Mounting Bracket
A-601 Manual Reset Switch