Model
CLS1 Capacitance Level Switch
provides reliable point level measurement of solids, liquids
and slurries in metallic or non-metallic tanks and vessels.
Model CLS1 detects the presence or absence of material in
contact with the probe by sensing a change in the capacitance.
Electronics provide highly sensitive measurement detection
(requires less than a 1 picofarad shift from ambient). State
of the art technology ignores material build-up on the vessel
sidewall or along the probe assembly. One time calibration
is simple with a single multi-turn potentiometer. Red LED
on housing indicates sensor status. Unit features an adjustable
1-30 second time delay and a 5 amp, SPDT fail-safe relay
output. Model CLS1 can be mounted vertically or horizontally.
APPLICATIONS
High or low level detection in bins, silos, tanks, hoppers,
chutes and other vessels where liquids, solids or slurries
are stored.
SPECIFICATIONS
Service: Solids, liquids, or slurries.
Wetted Material: CPVC.
Temperature Limits: Probe: -40 to 240°F (-40 to 116°C);
Electronics: -40 to 185°F (-40 to 85°C).
Enclosure Rating: NEMA 4X (IP56), PVC, dust tight,
water resistant.
Switch Type: SPDT.
Electrical Rating: 5A @ 250 VAC.
Power Requirements: 120 VAC, 1.5 VA.
Conduit Connection: 1/2" female NPT.
Process Connection: 1" male NPS.
Mounting Orientation: Vertical or horizontal.
Sensitivity: Adjustable to <1 pF.
Fail-Safe: Switch selectable, high/low.
Time Delay: Adjustable 1 to 30 seconds.
Weight: 2.0 lb (0.91 kg).
Agency Approvals: CE. |