Series
DA-7035N Temperature Switches include the same
time-proven switching mechanism used in our Series DA Pressure
Switches. Bourdon tube assures high sensitivity and long
life. Fully adjustable deadband makes units suitable for
a wide range of control applications. Visible, calibrated
dial and external adjustments make changing setpoints simple
and fast.
SPECIFICATIONS
Service: Compatible liquids or gases.
Wetted Materials: Bulb and connection: 304 SS.
Temperature Limit: Process: see model chart, Ambient:
180°F (82°C).
Pressure Limit: 300 psi (20.6 bar).
Enclosure Rating: General purpose. Optional weatherproof
and explosion-proof.
Repeatability: ± 1% of full scale.
Switch Type: SPDT snap switch. Optional DPDT snap
and a variety of mercury switches.
Electrical Rating: 15A @ 120/240/480 VAC. 1/8 HP
@ 120 VAC single phase. 0.5A @ 120 VDC resistive, 0.25A
@ 240 VDC resistive.
Electrical Connections: Screw terminal.
Conduit Connection: 7/8" (22.23 mm) hole for 1/2"
(12.7 mm) conduit hub.
Process Connection: 3/4" male NPT. Other sizes available.
Mounting Orientation: Vertical and level.
Set Point Adjustment: External knobs for set point
and reset point.
Weight: 5 lb (2.3 kg).
Deadband: Adjustable from minimum in model chart
to full range. Optional low fixed deadband.
Capillary: 6 ft (1.8 m) standard. Ranges 1N – 7N,
and 10N: copper. Ranges 8N, 9N, 11N: 304 SS.
Set Point Scale: Indication in °F and °C.
Options: See switch type, see enclosures, fixed deadband,
longer or shorter capillary, armored capillary, wells, two
stage, 1/2" or 1" connection sizes, manual reset, and other
bulb styles.
Agency Approvals: UL.
FEATURES
- Adjustable deadband
- Snap action switch standard
- Inert gas activated Bourdon tube
- No cross ambient temperature effects
- No bulb elevation correction required
- Visible dial calibrated in both °F and °C
- Visible on/off indication
|