Eliminate
traditional paper chart recorders with the Series
DL8 Process Data Logger. This versatile, multi-channel data
logger monitors and stores up to 32,768 process readings
for later download to an IBM compatible computer. Seven
external input channels easily interface with common transducer
and transmitter outputs. Internal thermistor measures ambient
temperature outputs. Internal thermistor measures ambient
temperature conditions. Programming is simple and easy with
the DL200 Windows® software and connecting cable (sold separately).
The Series DL8 Process Data Logger is ideal for monitoring
temperature, relative humidity, pressure, wind speed, current,
voltage and power.
SPECIFICATIONS
No. Of Channels: Eight; One for internal thermistor
and seven for external analog inputs.
Internal Thermistor Range: -40 to 158°F (-40 to 70°C).
Memory Size: 32,768 readings.
Accuracy: ±1% of full scale.
Clock Accuracy: ±8 seconds per day plus one sampling
interval.
Resolution: 8 bits (1 in 256).
Sampling Methods: Continuous (first-in, first-out)
or stop when full (fill-then-stop).
Sampling Rates: Selectable from 8 seconds to once
every 5 days.
Ambient Operating Temperature/RH: -50 to 160°F (-45
to 70°C), 0 to 95% RH, non-condensing.
Connection: Removable screw terminal.
Computer Requirements: IBM Compatible 386 or above
and Windows® 3.1 or later with 2 MB RAM and 2 MB hard disk
space, one serial port.
Power Requirements: Built-in 3.6V Lithium battery.
Power Consumption: 5-10 µA.
Housing Materials: PPE & PS (polyphenylene ether
& polystyrene).
Weight: 5 oz (110 g).
Agency Approvals: CE.
ACCESSORIES
-- See "Ordering" page
DL200 - Windows® Software
and Connecting Cable.
|