The DTS
Digital Temperature Switch is a low cost unit
that performs the functions of more expensive controllers.
The switch is designed for heating or cooling control. Twelve
different parameters can be programmed via the push button
front panel. The heating mode can be used to keep temperature
above a user-defined set point or alert an operator of a
low alarm condition. In contrast, the cooling mode can be
used to ensure process temperature stays below the critical
level or signal high alarm condition. View temperature,
error and alarm messaging on the bright red, 3-digit LED
display. Units accept PTC probe input (sold separately)
and include fitting clips for panel mounting and instruction
manual.
SPECIFICATIONS
Probe Range: -58 to 302°F (-50 to 150°C).
Input: PTC (1000O @25°C).
Output: amp SPDT or 16 amp SPST relay @ 250 VAC resistive,
(Depending on model).
Horsepower Rating (HP): 1/3 HP for 8 amp and 3/4
HP for 16 amp.
Power Requirements: 110 VAC.
Accuracy: ±1°C.
Display: 3-Digit, red.
Resolution: 1°.
Ambient Operating Temperature: 14 to 158°F (-10 to
70°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Agency Approvals: CE.
PARAMETERS
.
| |
Description |
Units |
Range |
| SP |
Set Point |
Degrees |
r1 to r2 |
| r0 |
Differential or
Hysteresis |
Degrees |
1 to 20 |
| r1 |
Lower Value Set
Point |
Degrees |
-50 to 150° |
| r2 |
Higher Value Set
Point |
Degrees |
-50 to 302° (-50
to 150°C) |
| d0 |
Heating or Cooling
Control |
Option |
Ht/Co |
| d2 |
Time for Defrosting |
Minutes |
0 to 59 min. |
| d8 |
Interval Time between
Defrosting |
Hours |
1 to 24 hr. |
| c0 |
Min. Stop Time
for Load |
Minutes |
0 to 59 min. |
| c1 |
Continuous Cycle
Time |
Hours |
0 to 24 hr. |
| P1 |
Ambient Probe Adjustment |
Degrees |
-10 to 10 |
| H5 |
Parameter Access
code |
Numeric |
0 to 99 (Set at
-00 from factory) |
| t0 |
Max. Temp on Display |
Degrees |
-50 to 302°F (-50
to 150°C) |
ACCESSORIES --
See "Ordering" Page
DTS-5 PVC Probe, 5 ft (1.5
m)
DTS-52 Metal Probe, 5 ft (1.5 m)
|