The Series
EPT-1 incorporates a quiet low-wattage poppet
valve and pressure sensor to measure and adjust the branch
line pressure proportional to the input. This unit has no
air consumption and is immune to mounting orientation and
supply line pressure fluctuations. The EPT-1M1 and EPT-1M2
incorporate a manual override switch, and in the manual
mode, the pressure can be increased or decreased with two
pushbutton switches. This feature is most desirable for
check out/commissioning and manual operation in case of
controller failure. Universal 24 VAC/24 VDC supply voltage
and field selectable 4 to 20 mA, 0 to 5 VDC, or 0 to 10
VDC inputs ensure single unit compatibility with most systems.
The unique steel chassis design substantially reduces the
overall size of the unit and, at the same time, provides
for ease of installation in a control panel directly or
with a snap track. A precision gage is provided for the
branch line pressure. A rugged aluminum manifold, brass
barb fittings, floating poppet solenoid valve, silicon pressure
sensor, and high performance electronics are some of the
features which make the Series EPT-1 the most reliable electro-pneumatic
transducer in the industry.
SPECIFICATIONS
Service: Clean dry air or any inert gas.
Input Signal: DC Current (4-20 mA) or DC Voltage (0-5/0-10).
Input Impedance: Current: 301 ohms; Voltage: 10K ohms.
Air Supply: 40 psig (276 kPa) maximum.
Accuracy: ±1% F.S. (includes linearity, hysteresis
and repeatability).
Pressure Drop: (Supply to branch) 0.1 psig (0.7 kPa).
Power Requirement: 18-28 VAC/VDC.
Current Consumption: 150 mA.
Temperature Limits: 25 to 150°F (4 to 65°C).
Thermal Effect: ±0.025%/°F (0.03%/°C).
Pressure Connections: 1/4" O.D. plastic tubing.
Electrical Connections: Screw terminals.
Wire Size: 12 Ga max.
Enclosure: 18 Ga C.R. steel chassis with baked on
enamel PMS2GR88B finish.
Weight: 1.0 lb (0.45 kg).
|