The Series
FLST Airflow Measurement Station is easy to install
-- simply connect the tubing to the station fittings, then
to a differential pressure manometer, gage, transmitter
or switch. Single or multiple airflow elements are factory
mounted and pre-piped in a casing designed for flanged connection
to the ductwork. Standard materials consist of a G90 galvanized
casing and 6063-T5 anodized aluminum flow sensors, suitable
for most HVAC applications.
The Series FLST utilizes an airflow averaging
element in a head-type device, generating a differential
(velocity) pressure signal similar to the orifice, venturi,
and other had producing primary elements. Strategically
located sensing ports continually sample the total and static
pressures when inserted normal to flow.
Total pressure sensed by the upstream ports
are continually averaged within the airflow element in an
isolated chamber. The static sensing ports are averaged
in a second isolation chamber. Multiple elements are joined
together for connection to a differential measurement device
(gage, transmitter, etc.) for flow measurement and indication
purposes.
How
to Order:

OPTIONS
- Consult Factory for Pricing
IM - Internal Pressure Connections.
F - (Oval Stations Only).
FEATURES
- Low signal-to-noise ratio.
- Multiple total and static pressure sensing ports along
the length of the element.
- Factory mounted and pre-piped in a flanged duct section
(casing).
- ±2% accuracy throughout velocity ranges of 100 fpm and
over.
- Standard construction includes galvanized casing and
6063-T5 anodized aluminum flow sensors.
- Standard airflow stations can be operated (in air) continuously
in temperatures up to 350°F or intermittently in temperatures
up to 400°F.
- All airflow stations can be operated in humidity ranges
of 0 to 100%.
- Standard airflow stations have good salt air resistance
and are suitable for most HVAC applications.
|