The Series
IP Current to Pressure Transducer converts a
current input signal to a linearly proportional pneumatic
output pressure. The features include built-in volume booster,
low air consumption, field reversible (provides output which
is inversely proportional to the input signal) and flexible
zero and span adjustments. The rugged NEMA 4X enclosure
allows splashdown and outdoor installation. The IP can be
used for applications that require operation of valve actuators,
pneumatic valve positioners, damper and louver actuators,
final control elements, relays, air cylinders, web tensioners,
clutches and brakes.
SPECIFICATIONS
Service: Oil free, clean dry air filtered to 40 microns.
Input Signal: 4-20 mA.
Input Impedance: IP-42: 180 ohms; IP-43 and IP-44:
220 ohms.
Air Pressure: Minimum: 3 psig (21 kPa) above maximum
output; Maximum: 100 psig (700 kPa).
Linearity: <±0.75% of span.
Hysteresis: <1% of span.
Repeatability: <0.5% of span.
Supply Pressure Sensitivity: <±0.1% of span per
psig (<±0.15% of span per 10 kPa).
Power Requirements: Loop powered.
Temperature Limits: -20 to 140°F (-30 to 60°C).
Pressure Connections: 1/4" female NPT.
Electrical Connection: 1/2" female NPT.
Air Consumption: 0.03 SCFM (0.5 m³/h) typical.
Output Capacity: 4.5 SCFM (7.6 m³/h ANR) at 25 psig
(175 kPa) supply; 12 SCFM (20 m³/h) at 100 psig (700 kPa)
supply.
Relief Capacity: 2 SCFM (3.4 m³/h) at 5 psig (35
kPa) above 20 psig (140 kPa) setpoint.
Weight: 2.1 lb (0.94 kg).
Agency Approvals: CE, FM.
|