The LCIA-01 Dual Relay Output Option Card plugs in most of the LCI108 and LCI108J Series, and all of the LCI208, LCI308, and LCI408 Series panel meter indicators and controls. This handy card adds two 8 Amp single pole double throw outputs to a panel meter.
SPECIFICATIONS
Relay Output: 2 SPDT relays rated
at 8 A @ 250 VAC resistive.
Maximum Power: 2000 VA, 192 W.
Maximum Voltage: 250 VAC, 150 VDC.
Contact Resistance: 3mO maximum.
Output Response Time: 10 ms maximum.
![]()
The LCIA-02 Quad Relay Output Option Card plugs in the LCI208, LCI308, and LCI408 Series panel meter indicators and controls. This handy card adds four 0.2 Amp single pole single throw outputs to a panel meter.
SPECIFICATIONS
Relay Output: 4 SPDT relays rated at 0.2
A @ 250 VAC resistive.
Maximum Power: 25 VA, 192 W.
Maximum Voltage: 250 VAC, 150 VDC.
Contact Resistance: 200mO maximum.
Output Response Time: 6 ms maximum.
![]()
The LCIA-03 Quad Transistor Output Option Card plugs in the LCI208, LCI308, and LCI408 Series panel meter indicators and controls. This handy card adds four NPN transistor outputs to a panel meter.
SPECIFICATIONS
Relay Output: 4 NPN Transistors rated at
50 mA @ 50 VDC max.
Leakage Current: 100µ max.
Output Response Time: 1 ms maximum.
![]()
The LCIA-04 Quad Transistor Output Option Card plugs in the LCI208, LCI308, and LCI408 Series panel meter indicators and controls. This handy card adds four PNP transistor outputs to a panel meter.
SPECIFICATIONS
Relay Output: 4 PNP Transistors rated at
50 mA @ 50 VDC max.
Leakage Current: 100µ max.
Output Response Time: 1 ms maximum.

The LCIA-06 Isolated Analog Retransmission Option Card plugs in the LCI208 Series panel meter indicators and controls. This handy card adds analog retransmission output to a panel meter. The output is 4 to 20 mA DC. (Not available for load cell.)
SPECIFICATIONS
Output: 4 to 20 mA DC into 500 ohms maximum.
Resolution: 12 bits.
Accuracy: 0.2% of full scale ±1 bit @ 23°C
±5°C (73°F ±9°F).
Response Time: 120 ms maximum.
Thermal Drift: 0.2µA/°C.
Isolation: Analog output to input signal,
3750V; Analog output to power and optional relay(s), 2300V.
![]()
The LCIA-10 RS-232/RS-485 Serial Communications Option Card plugs in the LCI208 Series panel meter indicators and controls. This handy card adds RS-232 or RS-485 Serial Communications to a panel meter.
SPECIFICATIONS
Output: RS-485, half duplex, 3 wire, vial
RJ-11 connector; and RS-232-C, full duplex, 4 wire, via
RJ-11 connector.
Protocol: Selectable ISO1745 (ASCII) or
Modbus® RTU Protocol.
Baud Rates: 1200 or 19200 baud, selectable.
Address Range: 0 to 99.