Designed
for use as a limit switch, fan control, or alarm
switch, Model M-51 is used on all types of air conditioning
ducts, furnaces, ovens, dryers, etc. Unit may also be used
with damper control system to prevent spread of fire through
ducts. Adjustments for both set and reset points. Visible
dial shows duct temperature and switch set points.
SPECIFICATIONS
Service: Compatible gases.
Temperature Limit: Process: range maximum, Ambient:
180°F (82°C).
Enclosure Rating: General purpose.
Switch Type: SPST mercury switch. Optional SPDT.
Electrical Rating: 10A @ 120 VAC/DC, 5A @ 240 VAC/DC.
3/4 HP @ 120/240 VAC single phase, 1/3 HP @ 120/240 VDC.
Electrical Connections: Screw terminal.
Conduit Connection: 7/8" (22.23 mm) hole for 1/2" (12.7
mm) conduit hub.
Process Connection: Mounting flange. Reversible for
flat or curved surfaces.
Mounting Orientation: Horizontal and level.
Set Point Adjustment: Internal moveable pointers
for set point and reset point.
Weight: 5 lb (2.27 kg).
Deadband: Adjustable from minimum in model chart
to full range.
Set Point Scale: Indication in °F standard. °C optional.
Options: SPDT and DPST switches. Switch that closes
on temperature increase.
Agency Approvals: UL and CSA. FM only on models M-51R-74
and MX-51R-75.
FEATURES
- UL Listed, CSA Certified.
- Automatic or Manual Reset.
- SPST Mercury Switch (SPDT Switches Available).
- Visible Dial Shows Duct Temperature.
- Two Adjustments: one sets high temperature set point,
the other sets low temperature reset.
|