The Series
SC1290 & SC1490 Thermocouple Limit/Alarm Switch Modules
are on-off or limit switches with selectable process signal,
thermocouple, or RTD inputs. Input type, scale range, output
action, and output type are all selectable by the user in
the field. All selections are made through easily accessible
switches without the need to open the product.
Each unit has two form C (SPDT) relays which
can operate independently, or be logically connected to
operate as a DPDT output. A two color LED indicator indicates
the status of each output relay.
These units mount easily on a standard 35
mm DIN rail. Low Voltage (SCLXXXX) units are also available.
SPECIFICATIONS
Power Supply: (SC units) 85 to 265 VDC/VAC 50 to
400 Hz (12-24 VDC, VAC 50-400 Hz for Low Voltage Option,
SCL units).
Isolation: 1500 V rms between outputs, input, and
power.
Set Points: Adjustable 0 to 100% of span.
Deadband: Adjustable 0.25 to 100% of span.
Drift: ±0.02%/°C typical ±0.05%/°C maximum.
Ambient Temperature Range: (Operating) 32 to 131°F
(0 to 55°C). (Storage) -40 to 176°F (-40 to 80°C).
Excitation Current: (SC1490) Cu10O = 5 mA; Plt 100O,
Ni 100O,Ni 120O = 500µA; Plt 500O, NiFe 1000O = 100 µA;
Plt 1000O = 50 µA.
Lead Compensation Error: (SC1490) = 0.02%/O.
Open Lead Protection: (SC 1490) Upscale only.
Input Impedance: (1290) 3 megohms.
Sensor Burnout Protection: Selectable, upscale or
downscale on 1290.
Relay Output: Form C, SPDT, one per set point, 5A
@ 250 VAC, resistive.
Latch Circuit Reset: Automatic at power up. Manual
with reset switch on front of module.
Indicators: One dual color LED per set point. Red
= relay on, green = relay off.
Wiring Terminals: Screw driven compression type.
Dimensions: 2.95" H x 0.89" W x 3.89" D (75 x 22.5
x 98.5 mm). |