Series
SI Smart Indicator is fully programmable and
accepts all commonly used temperature or process inputs.
Programming is via the front panel keys following a logical
menu structure which can be set to "short" (default) for
common usage features or "full" where the full range of
programmable features are available. The indicator can also
be programmed via a PC using the RS485 Modbus® communication
module. Password protection can be enabled to prevent any
unauthorized setting changes.
The Series SI features a 4-digit red LED
with selectable resolution. The display can be set to indicate
a fixed number of decimal places or auto scale for maximum
resolution. Optional interchangeable modules for relay,
4 to 20 mA retransmission, or Modbus® RS485 serial communication
output are easily installed without the need for dismantling
or recalibration.
Model SI-13 Smart Indicator is designed to
accept 2 or 3-wire Pt100O RTD or Types J, K, T, R, S, E,
F, N, or custom thermocouple inputs. Temperature measurements
can be displayed in selectable °F or °C. High/low scale
burnout, input filtering or smoothing, and offset can be
defined by the user. Select Model SI-23 Smart Indicator
for process signal input. The indicator has an internal
power supply to provide excitation to field transmitters.
Parameters such as input type, range, engineering units,
resolution, burnout condition, and filter time constant
can be easily programmed.
SPECIFICATIONS
General
Input/Output Isolation: 500 VAC RMS (galvanically isolated).
Display Range: -999 to 9999.
Output Impedance: 700 @ 24 VDC.
Power Supply: 90 to 253 VAC 50/60 Hz.
Ambient Operating Temperature: -22 to 140°F (-30
to 60°C).
Filtering: Off, 2 seconds, 10 seconds, or adaptive.
Time Constant (Filter Off): <1 second (to 63%
of final value).
Update Time: 250 msec maximum.
Weight: 2 lb (0.9 kg).
Model SI-13
Thermocouple Input Range: J: -328 to 2192°F (-200
to 1200°C); K: -328 to 2498°F (-200 to 1370°C); T: -328
to 752°F (-200 to 400°C); R and S: -14 to 3200°F (-10 to
1760°C); E: -328 to 1832°F (-200 to 1000°C); F: -148 to
1112°F (-100 to 600°C); N: -292 to 2372°F (-180 to 1300°C);
custom: ±9999.
RTD Input Range: Pt100O 2 or 3-wire: -328 to 1562°F
(-200 to 850°C).
Accuracy: T/C: ±0.04% full range input, ±0.04% rdg.;
RTD; ±0.01 full range input, ±0.05% of rdg.
Thermal Drift: Zero: 0.05µV/°F (0.1µV/°C), (RTD zero
drift is 0.008°F/°F); Span: 50ppm/°F (100ppm/°C).
Cold Junction Range: -40 to 185°F (-40 to 85°C).
Cold Junction Error: ±1°F.
Cold Junction Tracking: 0.05°F/°F (0.05°C/°C).
Excitation Current: 300µA to 550µA.
Maximum Lead Resistance: 50 ohms/leg.
Lead Resistance Effect: 0.004°F/ohm (0.002°C/ohm).
Model SI-23
Voltage Input Range: 0 to 1V, 1 to 5V, 0 to 10V.
Current Input Range: 0 to 20 mA, 4 to 20 mA, 0 to
10 mA.
Accuracy: ±0.05% full scale.
Thermal Drift: Zero: 0.05µV/°F ( 0.1µV/°C); Span:
50ppm/°F (100ppm/°C).
Excitation: 24V ±5% @ 50 mA.
Dual Relay Module
Contacts: Two changeover relays, common wiper.
Electrical Rating: AC: 253V; DC: 125V.
Maximum Load: AC: 7A @ 250V; DC: 7A @ 30V.
Maximum Power: AC: 1750VA; DC: 210W.
Connections: 5-way tension clamp connector.
4 to 20 mA Retransmission Module
Ranges: 0 to 10 mA, 0 to 20 mA, 4 to 20 mA (active
or passive).
Isolation: 500 VAC.
Accuracy: 0.07% full scale.
Maximum Output Load: Active: 1 K ohm; Passive: [(Vsupply-2)/20]
K ohm.
Max. External Supply: 30V (passive).
Connections: 5-way tension clamp connector.
RS485 Modbus® Communication Module
Physical Layer: 4-wire or 2-wire half duplex RS485.
Baud Rate: 19,200 or 9,600.
Protocol: Modbus RTU format.
Maximum Fan Out: 32 Units.
Connections: 5-way tension clamp connector.
ACCESSORIES
-- See "Ordering" Pages
Interchangeable Output Modules can quickly be connected to
the Smart Indicator and are automatically recognized. Dual
relay output module has two changeover relays with a common
wiper. Each relay can be set as high or low alarm independently.
An isolated retransmission module provides 0 to 10 mA, 0
to 20 mA, or 4 to 20 mA output in active (source) or passive
(sink) modes. The output can be any portion of the display.
The Modbus® serial communication module allows communication
with a PC for configuring or monitoring.