Temperature Switches
 

 

Monitor and control temperature in heating and cooling applications with the Series TCS Thermocouple Switch. The Series TCS offers a wide temperature range, two selectable alarm set, and an internal buzzer indicating alarm condition or error. The user can define set point, heating/cooling regulation, cycle time, alarm configuration, load status, and ambient probe adjustment. The thermocouple switch features password protection and error/alarm messaging. Temperature and output status is indicated on the bright red LED display. Use the configuration key (sold separately) to quickly program multiple units. The Series TCS includes a fitting clip for panel mounting, gasket, rear terminal cover and instruction manual.

APPLICATIONS
TS Digital Temperature Switches are suitable for industrial chillers, environmental chambers, walk-ins and freezers, heat sealers, sterilizers, beer and wine chillers, mug frosters, coolers, display cases and cabinets, warmers, meat and produce storage, floral preservation, refrigerated transportation, laboratories, food service equipment, ovens and dryers, tobacco preservation, hot melt glue stichers for case erectors, tool rooms, burn-in rooms and chambers, and cold water citrus packing.

SPECIFICATIONS
Probe Range: 0 to 700°C (32 to 999°F) for thermocouple J, 0 to 999°C (32 to 999°F) for thermocouple K,S.
Input: Type J, K, or S thermocouple depending on model.
Output: 15 A SPDT relay @ 250 VAC resistive.
Horsepower Rating (HP): 3/4 HP.
Control Type: ON/OFF.
Power Requirements: 110 VAC, 230 VAC or 12 VDC (depending on model).
Accuracy: ±1% FS.
Display: 3-digit, red, 1/2" (12.7 mm) digits, plus sign.
Resolution: 1°.
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 14 to 158°F (-10 to 70°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: NEMA 4X (IP65).
Agency Approvals: CE, UR Pending.

ACCESSORIES -- See "Ordering" Page

TS2-K Configuration Key

PARAMETERS

Description
Units
Range
SP
Set Point
Degrees
r1 to r2
r0
Differential or Hysteresis
Degrees
1 to 99°
r1
Lower Value Set Point
Degrees
0 to 999°
r2
Higher Value Set Point
Degrees
0 to 999°
d0
Heating or Cooling Control
Option
Ht/Co
c0
Min. Stop Time for Load
Minutes
0 to 59 min.
c2
Load Status During Probe Error
0/1
Off/On
P1
Ambient Probe Adjustment
Degrees
-10 to 10
P5
Ambient Probe Type
Option
J, K, or S
H5
Parameter Access Code
Numeric
0 to 255 (Set at 0 from factory)
A0
Alarm 1 Hysteresis
Degrees
1 to 999°
A1
Alarm 1 Threshold
Degrees
0 to 999°
A2
Alarm 1 Exclusion Time
Seconds
0 to 999°
A3
Alarm 1 Configuration
Option
Off, 1, or 2
A4
Alarm 2 Hysteresis
Degrees
1 to 999°
A5
Alarm 2 Threshold
Degrees
0 to 999°
A6
Alarm 2 Exclusion
Seconds
0 to 999°
A7
Alarm 2 Configuration
Option
Off, 1, or 2