Simultaneously
measure and control temperature and humidity
with the Series THC Temperature/Humidity Switch. The unit
offers a 3-digit red display for temperature indication
and a 3-digit green display indicating humidity. The Series
THC is equipped with four independent relays, two for temperature
control and two relays for humidity control.
The unit offers 61 programmable parameters for temperature
and humidity control including set point, differential,
direct/reverse acting, cycle time, alarm clock time, and
decimal point adjustment. In the event of a probe error,
the default operation of the relays can be set to open or
close. The THC features error or alarm messaging and password
protection.
The THC Temperature/Humidity Switch accepts up to two temperature
probe inputs (sold separately) and a humidity sensor. A
humidity sensor with 0-1V, 0-3V (sold separately), or 4-20
mA output can be used with the Series THC.
SPECIFICATIONS
Measurement Range: Temperature: -58 to 302°F (-50
to 150°C); Humidity: 0 to 100% RH.
Input: Up to 2 thermistors and 1 humidity sensor.
Output: 4 SPST, 8A relays @ 250 VAC.
Horsepower Rating (HP): 1/3 HP.
Control Type: On/Off direction, direct or reverse
acting, neutral.
Power Requirements: 110 or 230 VAC (depending on
model).
Accuracy: Temperature: ±0.5% of probe range; Humidity:
±3% of range.
Display: Two 3-digit displays. 1/2" digits.
Resolution: 0.1°.
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 32 to 158°F (0 to
70°C).
Storage Temperature: -4 to 176°F (-20 t 80°C).
Weight: 1.17 lb (530 g).
Panel Cutout: 5.15" x 2.37" (131 x 111 mm).
Front Panel Protection: NEMA 4X (IP65).
Agency Approvals: CE.
ACCESSORIES -- See "Ordering"
Page
THC-P Humidity Probe with 3V Output &
4 ft (1.2 m) cable
TS-5 Temperature Probe, PVC with 5 ft (1.5
m) cable
TS-6 Temperature Probe, Metal with 5 ft
(1.5 m) cable
TS-51 Temperature Probe, PVC with 10 ft
(3 m) cable
TS-61 Temperature Probe, Metal with 10
ft (3 m) cable
|