The TS
Digital Temperature Switch is designed to regulate
many heating and cooling applications. Easy programming
via the tactile front keypad enables quick setup of the
12 parameters for simple, reliable operation. The user can
define set point, heating/cooling regulation, hysteresis,
cycle time, ambient probe adjustment and defrosting time.
The unit features error or alarm messaging and password
protection. View probe temperature on the bright red, 3-digit
LED display. Select between 8 amp SPDT or 16 amp SPST relay
outputs, temperature display in °F or °C, and 110 VAC, 230
VAC, or 12 VDC power supplies. The Series TS includes a
thermistor with 5 ft (1.5 m) cable, fitting clips for panel
mounting, gasket, rear terminal cover, and instruction manual.
APPLICATIONS
TS Digital Temperature Switches are suitable for industrial
chillers, environmental chambers, walk-ins and freezers,
heat sealers, sterilizers, beer and wine chillers, mug frosters,
coolers, display cases and cabinets, warmers, meat and produce
storage, floral preservation, refrigerated transportation,
laboratories, food service equipment, ovens and dryers,
tobacco preservation, hot melt glue stitchers for case erectors,
cool rooms, burn-in rooms and chambers, and cold water citrus
packing.
SPECIFICATIONS
Probe range: -58 to 302°F (-50 to 150°C).
Input: 1.5-inch (4 cm) thermistor (1000O @ 25°C)
with 5 ft (1.5 m) cable.
Output: 8A SPDT or 16A SPST relay @ 250 VAC resistive
(Depending on model).
Horsepower Rating (HP): 1/3 HP for 8A and 3/4 HP
for 16A.
Control Type: ON/OFF.
Power Requirements: 110 VAC, 230 VAC or 12 VAC/VDC
(Depending on model). 4VA (230V).
Accuracy: ±1°C.
Display: 3-Digit, red, 1/2" digits.
Resolution: 1°.
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 14 to 158°F (-10 to
70°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: NEMA 4X (IP65).
Agency Approvals: CE, URc, UR
PARAMETERS
.
| |
Description |
Units |
Range |
| SP |
Set point |
Degrees |
r1 to r2 |
| r0 |
Differential or
hysteresis |
Degrees |
1 to 20 |
| r1 |
Lower Value Set
Point |
Degrees |
-50 to 150° |
| r2 |
Higher Value Set
Point |
Degrees |
-50 to 302°F (-50
to 150°C) |
| d0 |
Heating or Cooling
Control |
Option |
Ht/Co |
| d2 |
Time for Defrosting |
Minutes |
0 to 59 min. |
| d8 |
Interval Time between
Defrosting |
Hours |
1 to 24 hr. |
| c0 |
Min. stop time
for Load |
Minutes |
0 to 59 min. |
| c1 |
Continuous Cycle
Time |
Hours |
0 to 24 hr. |
| P1
| Ambient Probe Adjustment |
Degrees |
-10 to 10 |
| H5 |
Parameter Access
code |
Numeric |
0 to 99(Set at
-00 from Factory) |
| t0 |
Max. Temp. on Display |
Degrees |
-50 to 302°F (-50