Temperature Switches
 

 

Monitor and control temperature for heating and cooling applications with the Series TS2 Digital Temperature Switch. The Series TS2 offers twelve programmable functions to customize the unit to fit application requirements. Use the 15(5) Amp SPDT relay output to drive a motor, compressor, or fan. Designed with the OEM in mind, the TS2 offers the ability to configure multiple units with the touch of a button.

Programming multiple units is quick and easy. Simply program one switch with the desired parameter settings and connect the configuration key (sold separately) to the back of the unit. Press the button on the configuration key and download the parameter settings. Connect the key to the other switches to upload the stored settings with the push of a button.

The TS2 features set point adjustments, static defrost timing, compressor mean time, hysteresis, and ambient probe adjustment. Security protection is offered using a password code. The Series TS2 Digital Temperature Switches are designed to operate with PTC (1000 O @ 25°C) probes sold separately.

SPECIFICATIONS
Probe range: -58 to 302°F (-50 to 150°C).
Input: PTC thermistor 1000O @ 25°C.
Output: 15A SPDT relay @ 250 VAC resistive 5A inductive.
Horsepower Rating (HP): 3/4 HP.
Control Type: ON/OFF.
Power Requirements: 110 VAC.
Accuracy: ±1% FS.
Display: 3-Digit, red, 1/2" digits.
Resolution: 1°.
Memory Backup: Nonvolatile memory.
Ambient Operating Temperature: 14 to 131°F (-10 to 55°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Weight: 2.3 oz (65 g).
Front Panel Rating: NEMA 4X (IP65).
Agency Approvals: CE, URc, UR.

ACCESSORIES -- See "Ordering" Page

TS-5 PVC Probe, 5 ft (1.5 m) cable
TS-51 PVC Probe, 10 ft (3 m) cable
TS-6 Metal Probe, 5 ft (1.5 m) cable
TS-61 Metal Probe, 10 ft (3 m) cable
TS2-K Configuration Key

PARAMETERS

Description
Units
Range
SP
Set point
Degrees
r1 to r2
r0
Differential or hysteresis
Degrees
1 to 20
r1
Lower Value Set Point
Degrees
-50 to 150°C (-50 to 302°F)
r2
Higher Value Set Point
Degrees
-50 to 150°C (-50 to 302°F)
d0
Heating or Cooling Control
Option
Ht/Co
d2
Time for Defrosting
Minutes
0 to 59 min.
d8
Interval Time between Defrosting
Hours
1 to 24 hr.
c0
Minimum Stop Time for Compressor
Minutes
0 to 59 min.
c1
Continuous Cycle Time
Hours
0 to 24 hr.
P1
Ambient Probe Adjustment
Degrees
-10 to 10
H5
Parameter Access code
Numeric
0 to 99
t0
Maximum Temperature on Display
Degrees
-50 to 150°C (-50 to 302°F)