Switches |
| |
| |
Rugged
and reliable the Series V4 Flotect® flow switch
operates automatically to protect equipment and pipeline
systems against damage from reduction or loss of flow. The
V4 is time tested being installed in thousands of pipelines
and processing plants around the world. A unique magnetically
actuated switching design gives superior performance. There
are no bellows, springs, or seals to fail. Instead, a free-swinging
vane attracts a magnet within the solid metal switch body,
actuating a snap switch by means of a simple lever arm.
APPLICATIONS
- Protects pumps, motors and other equipment against low
or no flow
- Controls sequential operation of pumps
- Automatically starts auxiliary pumps and engines
- Stops liquid cooled engines, machines and processing
when coolant flow is interrupted
- Shuts down burner when air flow through heating coil
fails
- Controls dampers according to flow
SPECIFICATIONS
Service: Gases or liquids compatible with wetted
materials.
Wetted Materials:
Vane: 316 SS.
Body: Brass or 316 SS standard.
Magnet Keeper: 430 SS standard,
316 SS optional.
Options: Other materials also available,
consult factory (e.g. PVC, Hastelloy, Nickel, Monel, Titanium).
Temperature Limit: -4 to 275°F (-20 to 135°C) standard,
MT high temperature option 400°F (205°C) [MT option not
UL, CSA, ATEX or SAA].
Pressure Limit: Brass body 1000 psig (69 bar), 316
SS body 2000 psig (138 bar), optional 5000 psig (345 bar)
available with 316 SS body and SPDT switch only.
Enclosure Rating: Weatherproof and Explosion-proof.
Listed with UL and CSA for Class I, Groups C and D; Class
II, Groups E, F, and G. ATEX 0344 II 2 G EEx d
IIB T6 -20°C=Tamb=75°C, EC-Type Certificate No.: KEMA 03ATEX
2383. SAA: Exd C T6 (T amb=60°C), Zone I. Also FM approved.
Switch Type: SPDT snap switch standard, DPDT snap
switch optional.
Electrical Rating: UL, FM ATEX and SAA models 10A
@ 125/250 VAC. CSA models: 5A @ 125/250 VAC; 5A res., 3A
ind. @ 30 VDC . MV option: 1A @125 VAC; 1A res., .5A ind.
@ 30 VDC. MT option: 5A @ 125/250 VAC. [MT and MV option
not UL, CSA, FM, ATEX or SAA].
Electrical Connections: UL and CSA models: 16 AWG,
6" (152 mm) long. ATEX and SAA unit: Terminal block.
Conduit Connection: 3/4" female NPT.
Process Connection: 1-1/2" male NPT.
Mounting Orientation: Within 5° of vertical for proper
operation. Units for horizontal installation (vertical pipe
with up flow) available.
Set Point Adjustment: For universal vane: five vane
combinations.
Weight: 4 lb 8 oz (1.9 kg).
Agency Approvals: UL, CSA, CE, FM, SAA and ATEX.
|
V4 Universal Vane Flow Charts
Values shown
in both charts are nominal. If normal flows exceed actuation
rates by less than 10%, custom vanes are recommended. Figures
are based on standard vertical installation in a 1-1/2"
thredolet in a horizontal run of pipe.

Actuation rates are based on cold water at a specific gravity of
1.0. For fluids of different specific gravity, actuation
rates may be approximated by dividing the rate shown by
the square root of the specific gravity
.
Actuation rates are based on air at standard conditions. For gases
at other pressures, temperatures, or specific gravities,
consult factory for equivalent flow approximations.
|
| OPTIONS
- Consult Factory for Pricing -D
- DPDT contacts.
-MV - Gold Plated Contacts, options for dry
circuits see electrical rating in specification, no listings
or approvals).
-MT - High Temperature, option rated 400°F
(204°C) see electrical rating in specifications, no listings
or approvals.
-TRI - (increasing flow); -TRD
- (decreasing flow), Time Delay Relay, option with 2 SPDT
contacts, adjustable from 0-1 to 0-31 minutes. (no listings
or approvals).
-316 - 316 SS Magnet Keeper, option to replace
standard 430 SS.
-SAA - SAA, listed construction.
-V - Vertical Up Flow, option for upward
flow in vertical pipe.
-AT - Atex listed construction.
Consult
factory for price and availability
of fittings for V4 installation. Thredolets, bushings, and
tees are available in a variety of sizes and materials.
For custom vane models, please
supply factory with following information: pipe size, flow
direction (horizontal, up), mounting, pressure, temperature,
specific gravity, flow rates (maximum normal, actuation/deactuation*),
etc.
*When both values are supplied, note which is
critical.
APPLICATION
DRAWINGS FOR FLOTECT® AUTOMATIC FLOW SWITCHES

|
FEATURES
- Leak proof body machined from bar stock
- Choice of custom vane calibrated for
your application, Model V4, or field adjustable multilayer
vane, Model V4-2-U (see Vane Flow Chart on "Specifications"
page)
- Weatherproof, designed to meet NEMA
4
- Explosion-proof (listing included, see
"Specifications" page)
- Installs directly and easily into pipeline
with a thredolet, tee, or flange (see Application Drawings
on "Options/Accessories" page)
- Can be used in pipes 1-1/2" and up
- Electrical assembly can be easily replaced
without removing the unit from installation so that the
process does not have to be shut down
- High pressure rating of 1000 psig (69
bar) with the brass body and 2000 psig (138 bar) with the
316 SS body
INSTALLATION

|
| |
|
DIMENSIONAL DRAWING |
V4

|
| |
|
Service
Manual |
| |
|
CATALOG |
| |
|
ORDERING |
| |
|
|
|
|